This page explains, in plain terms, how we go from the four raw Excel files to alerts with a € and CO₂ value, and why we made each choice. The experiments behind the choices are in the experiment log; every column is described in the data dictionary.
4 raw Excel files (one per zone)
│ 1. combine and unify src/save_parquet.py (loader.py, unify.py)
│ 2. build one hourly table ** script missing in the repo **
│ 3. clean (rules R1–R12) src/clean.py
│ 4. add calendar src/build_calendar.py
│ 5. add outdoor weather src/download_weather.py
│ 6. add electricity prices src/download_price_omie.py
│ 7. merge everything src/merge_external.py
│ 8. freeze dataset v1 src/freeze_dataset.py → data/processed/cedint_hourly_v1.parquet
▼
Notebook 01 Exploration: what drives electricity use?
Notebook 02 Expected use per circuit (baselines → Ridge → LightGBM)
Notebook 03 Alerts, chronic waste, € and CO₂ → reports/*.csv (input for the dashboard)
Notebook 04 Model search (7 model types, month-by-month check) → final LightGBM settings
(04_model_search, uses the cleaned zone files data/zone_*_hourly.parquet via src/zones.py)
Notebook 04 90 % prediction band per circuit → reports/interval_bands.parquet
(04_prediction_interval)
Notebook 05 Prophet compared with LightGBM
▼
Dashboard dashboard/app.py (Streamlit, 7 pages) reads data/processed/ and reports/
Two notebooks share the number 04 because they were written in parallel.
Each step writes a file that the next step reads, so any step can be re-run on its own.
The frozen dataset comes with a MANIFEST.json that stores a fingerprint (SHA-256) of every input and output file,
so anyone can check that they are using exactly the same data. pytest runs automatic checks on it
(no duplicate hours, correct grid, no leakage in the features).
Known gap: step 2 (turning the 2025 minute readings into hours and building the hourly table) was done, but its script is not in the repo yet. Until it is pushed, the pipeline cannot be rebuilt from the raw files.
| Period A | Period B | |
|---|---|---|
| Dates | 2 Apr 2020 – 28 Feb 2023 | 18 Aug – 13 Oct 2025 |
| Readings | one reading per hour | up to one per minute, averaged to one value per hour |
| Hours | 25,489 | 1,341 |
There is no data at all between March 2023 and August 2025 (901 days). This gap is in the source files. Because of it, the two periods are never joined: features that look back in time (e.g. “last week”) stop at the gap. Period A is used to build the models, period B to check them on recent data.
| Rule | Problem found | Decision | Why | Values touched |
|---|---|---|---|---|
| R1 | Timestamps have no time zone | Treated as UTC; Madrid local time added | No jumps at the daylight-saving changes, and light sensors match sunrise and sunset in UTC (src/check_utc.py) |
all rows |
| R2 | Some hours are missing | Complete hourly grid; missing hours left empty | So every analysis sees the gaps instead of skipping them | 524 empty hours |
| R3 | Two circuits measure nothing useful | SE Projector (always 0) and SW RACK (stops 3 Dec 2021) removed | No information | 2 circuits |
| R4 | NW Emergency Lighting is negative 97.7 % of the time | Sign flipped | The meter is wired in reverse; a lamp cannot produce energy | 24,230 |
| R5 | Small negative values (−10 to 0 W) | Set to 0 | Meter noise around zero | 31,870 |
| R6 | Larger negative values (below −10 W) | Set to empty | Not noise; a real error | 4 |
| R7 | Same non-zero value for 6+ hours | Set to empty (period A) | A stuck sensor | 0 found |
| R8 | 6+ hours of exact 0 on a circuit that normally uses power | Set to empty | Sensor off, not real zero use | 3,694 |
| R9 | Temperature, humidity and light all 0 together | Set to empty | Sensor failure | safeguard |
| R10 | Indoor temperature of 739–1,411 °C (SW, 1–7 Mar 2022) | Values outside the allowed range set to empty | Impossible values | see note below |
| R11 | 2025 hours built from few minute readings | Flagged low_coverage (kept) |
The hourly average is less reliable | 611 |
| R12 | Totals in the raw file include bad values | Zone and storey totals recalculated from clean circuits, only when all circuits are present | A total with a missing part would look like a drop in use | all totals |
| Finding | Decision | Reason |
|---|---|---|
Energy counters (Ea, Er) reset and jump |
Not used at all; energy per hour is taken from the average power W |
Where the counters work, both give the same result (ratio 1.00), and W has no resets |
| Presence sensors stuck at 1.0 for weeks (NW, SE, SW) | Kept, but not used in models or conclusions | Presence cannot be 100 % for 83 days; this is a sensor fault |
| SW humidity identical for up to 71 days | Kept, not used | Stuck or insensitive sensor |
| NE Plugs drops from about 190 W to 25 W for whole days (10 periods) | Kept | Plausible (load switched off) but cannot be confirmed |
| NW Plugs peaks up to 8.25 kW in January 2023 | Kept | Neighbouring hours are consistent, so they look real (heaters) |
| COVID lockdown (spring 2020) | Kept in the data, flagged, left out of model training | The building was not used normally |
src/clean.py removes indoor temperatures outside 5–45 °C.
The cleaned Excel file uses 0–45 °C and keeps 70 hours of 3.8–5 °C in January 2021 (a real cold wave).
We should agree on one value.src/clean.py. Agree whether to add it.To say that something is wasted, we first need to know how much each circuit normally uses at a given hour. The model predicts this expected use; the gap between actual and expected is what we look at.
| What we predict | energy used per hour per circuit (Wh), one day ahead |
| Circuits | 9 “focus” circuits: Plugs & Sockets (all 4 zones), Lighting (NW, SW, SE), HVAC (NW, SE) |
| Information the model uses | hour, day of the week, working day / holiday / break, season, outdoor temperature (and how far it is below or above a comfortable level), sunlight, humidity, and the circuit’s own use 1 day, 2 days, 1 week and 2 weeks earlier |
| Information it may not use | anything from the same hour (that would be cheating), indoor sensors (they are effects of the use, not causes), anything across the 2023–2025 gap |
| Final model | LightGBM (gradient-boosted decision trees), one model per circuit, all with the same settings (reports/final_model_settings.json) |
| Why this model | out of seven model types (linear, Ridge, Lasso, decision tree, random forest, LightGBM, neural network), LightGBM has the lowest error in a month-by-month check over 15 months and wins most months. A neural network and a random forest come close, and Ridge is not far behind, which shows the model is not over-complicated. Prophet, a well-known forecasting tool, is worse on every circuit. |
| Why one day ahead | predicting one hour ahead is more accurate, but such a model quickly “gets used to” a heater left on and stops warning; a model that only knows yesterday keeps warning |
| How we tested | trained on Jun 2020 – Aug 2022, settings chosen on Sep – Dec 2022, then month by month from Sep 2021 to Dec 2022, tested once on Jan – Feb 2023, then checked on Aug – Oct 2025 |
| Uncertainty | a 90 % band around the prediction (quantile LightGBM with a rolling 28-day correction); on the test months 89 % of the hours fall inside it. Shown in the dashboard’s “Expected vs actual” page. |
| Main metric | MAE in kWh: the average miss, in the unit the client thinks in |
Honest limitation: hour by hour, the model is still off by more than the 30 % that the industry guideline ASHRAE 14 asks for, on most circuits. The main reason is people: heaters and lights are switched on and off by hand. For finding large waste this is good enough (see the synthetic test below), but it should be said in the presentation.
All experiments behind these choices, with their numbers, are in the experiment log (EXP-03 to EXP-05 and EXP-10 to EXP-13).
Still open: notebook 03 and the dashboard export still use the per-circuit settings of notebook 02 (reports/model_params.json).
The difference is very small (0.181 against 0.182 kWh per hour on the test months), but it should be aligned.
We use two signals, because one model cannot see everything.
Tested with fake loads: we added 40 fake “forgotten devices” at night (1 kW on plug circuits, 300 W on lights and HVAC) and checked whether the detector found them. It found 100 % on 7 of the 9 circuits. On NW Plugs, the noisiest circuit, one heater is found only 30 % of the time, but 2 kW is found 92 % of the time.
A model that looks at last week’s use slowly learns repeated waste (heaters on a timer every weekend) as “normal”. So we add a simple, transparent rule:
| Severity | Excess energy per event |
|---|---|
| Low | under 2 kWh |
| Medium | 2 – 10 kWh |
| High | over 10 kWh |
Thresholds are in params.yaml and can be changed without touching the code.
| How | Source | |
|---|---|---|
| € (lower bound) | excess kWh × hourly wholesale price | OMIE (energy only, no network costs or taxes) |
| € (all-in) | excess kWh × €0.142/kWh | Eurostat non-household price |
| CO₂ | excess kWh × hourly CO₂ intensity of the Spanish grid (column co2_intensity_g_kwh) |
Red Eléctrica ESIOS indicator 10355, from the cleaned zone files. Alternative in params.yaml: yearly CNMC supplier-mix factor (259–273 g/kWh), about twice as high |
Events during working hours are shown as “to investigate” but not counted as savings, because part of that use is legitimate.
| File | Content |
|---|---|
reports/anomaly_events.csv |
one row per event: circuit, start, end, excess kWh, €, kg CO₂, severity, message |
reports/offhours_waste_daily.csv |
chronic waste per circuit per day |
reports/savings_summary.csv |
potential savings per zone, circuit and year |
| Year | Potential savings (9 focus circuits) | € | CO₂ |
|---|---|---|---|
| 2021 | 7.2 MWh (32 % of their use) | €750 – 1,020 | 0.8 t |
| 2022 | 6.1 MWh (27 % of their use) | €860 – 1,010 | 0.8 t |
Biggest lever: electric heaters on the NW plug circuits at night, at weekends and in breaks (3–4 MWh per year), then the NW lights that are on every night 22:00–07:00 (about 1 MWh per year).