Data dictionary — cedint_hourly_v1 (KAN-129)

This page describes every column of the frozen modelling dataset data/processed/cedint_hourly_v1.parquet: what it means, its unit, and where it comes from. Technical details (checksums, build steps, missing shares) are in data/processed/MANIFEST.json.

The dataset in short

   
One row = one hour on Storey 1 of the CeDInt building (UPM, Montegancedo campus)
Rows / columns 26,830 rows · 64 columns
Period A (Regime A) 2 Apr 2020 – 28 Feb 2023, hourly readings (25,489 rows)
Period B (Regime B) 18 Aug 2025 – 13 Oct 2025, minute readings combined into hours (1,341 rows)
Gap No data between March 2023 and August 2025. This gap is in the original files, not caused by cleaning.
Missing hours Kept as empty rows, never filled in (cleaning rule R2)

How to read the electricity columns

Electricity columns are named ZONE|Circuit W, for example NW|Plugs & Sockets W.

We use this average power instead of the meters’ own energy counters (Ea), because those counters sometimes reset or jump. Both give the same result where the counters work correctly.

1. Time columns

Column Meaning Unit / values
timestamp_utc Start of the hour in UTC (the time zone of the raw files, checked against sunrise and sunset in src/check_utc.py) date and time
timestamp_local Same hour in Madrid local time, including summer time date and time
date_local Local date date
weekday_local Day of the week, local time 0 = Monday … 6 = Sunday
hour_local Hour of the day, local time 0–23
month Month 1–12
Regime Which data period the row belongs to A (2020–23, hourly) or B (2025, minute data)
low_coverage Period B only: the hour was built from fewer than 30 one-minute readings, so treat it with care (rule R11) True / False

2. Electricity per circuit (16 circuits)

All values: average power in the hour [W] = energy in that hour [Wh]. “Missing” is the share of hours without a usable value.

Column What it is Missing Notes
NE\|HVAC W Heating, ventilation and air conditioning, zone NE 2.0 %  
NE\|Plugs & Sockets W Wall sockets (computers, screens, portable heaters…), zone NE 2.0 %  
NW\|Emerg. Lighting W Emergency and exit lighting, zone NW 13.0 % Must run 24/7, not counted as waste. Meter was wired in reverse; sign corrected (R4)
NW\|HVAC W Heating, ventilation and air conditioning, zone NW 7.6 %  
NW\|Hand Dryer W Hand dryers, zone NW 2.0 % Small, short bursts of use
NW\|Lighting W Ceiling lighting, zone NW 2.0 % On every night 22:00–07:00 (see EDA)
NW\|Plugs & Sockets W Wall sockets, zone NW 2.0 % Largest consumer of the floor (about 45 %); rises sharply in cold weather
NW\|RACK W Server / network rack, zone NW 2.0 % Must run 24/7, not counted as waste
SE\|Emerg. Lighting W Emergency and exit lighting, zone SE 7.7 % Must run 24/7, not counted as waste
SE\|HVAC W Heating, ventilation and air conditioning, zone SE 7.6 %  
SE\|Lighting W Ceiling lighting, zone SE 4.1 %  
SE\|Plugs & Sockets W Wall sockets, zone SE 8.3 %  
SW\|Emerg. Lighting W Emergency and exit lighting, zone SW 4.9 % Must run 24/7, not counted as waste
SW\|Hand Dryer W Hand dryers, zone SW 4.9 %  
SW\|Lighting W Ceiling lighting, zone SW 5.2 %  
SW\|Plugs & Sockets W Wall sockets, zone SW 4.7 %  

Two circuits from the raw files were removed (rule R3): SE|Projector (always 0) and SW|RACK (stops sending data in December 2021).

3. Totals

Totals are recalculated from the cleaned circuits, and only for hours where every circuit of that zone has a value (rule R12). That is why they have more missing hours than the single circuits.

Column What it is Missing
NE\|ZONE TOTAL W Sum of all circuits in zone NE 2.0 %
NW\|ZONE TOTAL W Sum of all circuits in zone NW 13.0 %
SE\|ZONE TOTAL W Sum of all circuits in zone SE 11.4 %
SW\|ZONE TOTAL W Sum of all circuits in zone SW 6.4 %
STOREY1\|TOTAL W Sum of the four zones 21.4 %

Unit: average power in the hour [W] = energy in that hour [Wh].

4. Indoor environment sensors (zones NW, SE, SW)

Column pattern Meaning Unit Notes
ZONE\|ENV Temp °C Indoor temperature °C Values outside 5–45 °C removed (R10)
ZONE\|ENV Hum %RH Indoor relative humidity %  
ZONE\|ENV Lum lux Indoor light level lux  
ZONE\|ENV Pres share Share of the hour in which presence was detected 0–1 Not reliable: sensors get stuck for weeks and do not follow working hours. Not used in the models.

If temperature, humidity and light are all exactly 0 at the same time, the reading is treated as missing (R9). Indoor temperature and light are partly caused by the electricity use (heaters, lamps), so they are not used to predict it.

5. Outdoor weather

Source: Open-Meteo historical archive for the Montegancedo campus (src/download_weather.py).

Column Meaning Unit
wx_temp_c Outdoor temperature °C
wx_feels_like_c Felt temperature °C
wx_humidity_pct Outdoor relative humidity %
wx_precip_mm Rain / precipitation in the hour mm
wx_cloud_pct Cloud cover %
wx_wind_ms Wind speed m/s
wx_solar_wm2 Sunlight reaching the ground W/m²
wx_pressure_hpa Air pressure hPa

6. Calendar

Source: src/build_calendar.py. All flags are True / False for the local date.

Column Meaning
is_weekend Saturday or Sunday
is_holiday_national_madrid National or Community of Madrid public holiday
is_holiday_madrid_city Madrid city holiday
is_upm_nonteaching_day UPM-specific day without teaching (e.g. Santo Tomás)
is_holiday Any of the three holiday flags above
is_christmas_break UPM Christmas break
is_holy_week Holy Week (Semana Santa)
is_august_closure August closure
is_break Any of the three break flags above
is_working_day Not a weekend, holiday or break
is_covid_lockdown COVID-19 lockdown (until 21 June 2020). Separate flag, not included in is_working_day; these weeks are left out of model training
holiday_name Name of the holiday, if any
academic_year UPM academic year, starting in September (e.g. 2021-22)

⚠️ To check: the Christmas break and August closure dates look too wide in places (normal working days appear on 2 Jan 2023, and lighting is used on weekdays in August 2025). See docs/STATUS_AUDIT.md.

7. Electricity price

Source: OMIE, the Spanish day-ahead electricity market (src/download_price_omie.py).

Column Meaning Unit
price_eur_mwh Wholesale electricity price for that hour. Energy only: no network costs or taxes, so the real cost is higher. € per MWh
price_eur_mwh_is_fallback True when OMIE had no price for that hour and the monthly average was used instead. If a month has fewer than 7 days of real prices, the hours stay empty. True / False

The CO₂ factor and the all-in price used for the € and CO₂ figures are not in this dataset; they are set in params.yaml.

Cleaning rules referred to above

Rule What it does
R1 Raw timestamps treated as UTC; Madrid local time added
R2 Complete hourly grid; missing hours left empty, not filled in
R3 Dead circuits removed (SE Projector, SW RACK)
R4 NW emergency lighting sign flipped (meter wired in reverse)
R5 Small negative values (−10 to 0 W) set to 0
R6 Large negative values (below −10 W) set to missing
R7 Same non-zero value for 6 hours or more (stuck sensor) set to missing (period A)
R8 6 hours or more of 0 on a circuit that normally uses power set to missing
R9 Temperature, humidity and light all 0 together set to missing
R10 Indoor temperature outside 5–45 °C set to missing
R11 Period B hours built from fewer than 30 minute readings flagged low_coverage
R12 Zone and floor totals recalculated from clean circuits